> Large setting range

  

  > Small size

  > Simple to mount

  > High switching performance

  DMO 1140: Thermostat (normally closed); contact breaker for regulating heaters. The contact opens when temperature

  is rising

  .

  DMS 1141: Thermostat (normally open); contact maker for regulating of filter fans and heat exchangers or for switching

  signal devises when temperature limit has been exceeded. The contact closes when temperature is rising

  .DMO 1140 / DMS 1141

  Switch temperature difference

  +/-5°C

  Sensor element

  thermostatic bimetal

  Contact type

  snap-action contact

  Service life

  > 100,000 cycles

  Max. switching capacity

  250VAC, 10 (2) A / 120VAC, 15 (2) A

  DC 30W at 24VDC to 72VDC

  Max. inrush current

  AC 16A for 10 sec.

  Connection

  2-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm2 (AWG 14)stranded wire1 1.5mm2 (AWG 16)

  Mounting

  clip for 35mm DIN rail, EN 60715

  Casing

  plastic according to UL94 V-0, light grey

  Dimensions

  60 x 33 x 43mm

  Weight

  approx. 40g

  Fitting position

  variable

  Operating/Storage temperature

  -45 to +80°C (-49 to +176°F)

  Operating/Storage humidity

  max. 90% RH (non-condensing)

  Protection type

  IP20

  1When connecting with wires, wire end ferrules must be used.

  important note: The contact system of the regulator is subjected to environmental influences, thus the contact

  resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.